Air tightness report carried out on a structure insulated using Biofoam 800

EcoEfficiency Ireland

EcoEffeciency
castlebar House

AIR TIGHTNESS TEST

Pontoon Road, Castlebar,
Co. Mayo.
Client: Biofoam Spray Insulation
Date of inspection: Friday, 30th October, 2009
Time of inspection: 3.30pm until 6.45pm
Outside temp at time of inspection: 15.4c
Inside temp: 19.6c in kitchen Relative humidity in kitchen: 74% Your ref: PO 1044
Contact: Aaron from BFSI
Our ref: POH 1044
Operator: Paul Garvey
Report date: Wednesday, 4th November, 2009

LEAKAGE AND FLOW ESTIMATES  

Leakage Area:
ELA-CGSB @ 10 Pa:
ELA - LBL @ 4 Pa:
Leakage Ratio @ 10 Pa:

50 Pa Flow:
ACH @ 50 Pa:
Flow @ 50 Pa:
Permeability Index @ 50 Pa

Infiltration:
Estimated Annual Infiltration
Infiltration total flow:
Infiltration/Occupant:
Infiltration/Bedroom:
Infiltration DEAP Index:


843.7 cm2
461.6 cm2
3.042 cm2 leakage/m2


3.161 air changes per hr
2047. m3/h
1.657 m3/h/m2


0.158 changes per hour
102.3 m3/h
25.59 m3/h/occupant
25.59 m3/h/bedroom
0.0828 m3/h/m2